Ultra Electronics, Nuclear Sensors & Process Instrumentation (Weed Instrument)
Modbus Remote I/O Electrical Interface, 2C14 module
Type:
Modem
Description:
Modular device to connect end devices over fiber optic cable using Modbus Remote I/O protocol.
Connectivity:
Modbus
Features:
The 2C14 provides electrical interface for Modicon Remote I/O by conditioning the electrical signals supplied to and from Modicon equipment for transmission over the fiber optic network. The simplest modem configuration consists of a Power Supply, an Electrical Interface, and an Optical Interface Module. Additional modules may be added to configure Daisy Chain, Star, Self-Healing Ring topologies and provide Redundancy. A maximum combination of five optical or electrical modules may be connected together in one modem, inter-module communications and operating power is achieved through the integrated module backplane connections.
Specifications:
Mounting: 35mm DIN Rail; Weight: < 9oz ( 250g ); Baud Rate: 1.54M Baud; Copper Cable Connector: F-Type; Copper Cable End Termination: Internal, 75 Ohms; Maximum Copper Cable and Tap; Loss Cannot Exceed: 20 dB; Power Indicator: Green LED; Communications Activity Indicator: Amber LED; Ambient Conditions: -40 to 85?C Operational Temperature Range