Type:  Misc. Hardware
Description:  Microprocessor-based overload relay, designed to provide protection for 3-Phase AC motors. It offers a broad range of features in a compact package for monitoring and managing motor performance.
Connectivity:  Modbus
Features:  Actual motor operating conditions are accessed by the scrolling menu and viewed by a two-line highly visible vacuum fluorescent display. Fault conditions are displayed indicating the specific cause of the occurring fault. Available with RS 485 Modbus serial connectivity.
Specifications:  Input Voltage: 200-500 VAC 3-Phase (Nominal); Frequency: 50/60 Hz; Phase Sequence: ABC (will not operate CBA); Output Contact: DPDT; Form "C" 10 A @ 240 VAC; Alarm Output: SPDT; Form "C" 10 A @ 240 VAC; Control Voltage: None Required; RELAY ACCURACY; Voltage: ?1% Current: ?1% G.F. Current ?10% Timing 5% ?1 Second