Type:  I/O Module
Description:  The MT1 Modbus converts 4 analogue input signals to digital data, based on Modbus RTU and transmits them via RS485. The 4 inputs are selectable from current, voltage, resistance and temperature. Any combination of inputs is possible from one input of each type to 4 times the same input. The MT1 has a USB port for easier settings and firmware updates.
Connectivity:  Modbus
Features:  4 analogue inputs; Modbus RTU output via RS485; User configurable linear scaling of each signal separately; Free firmware updates: last version always available on company website; Free setting/signal reading SW; 4 bicolor LED diodes to set for various functions including on/off, working, communication status, errors or alarms; Software and manuals delivered in an 8 GB flash disc
Specifications:  Selectable inputs from: 0-25 mA, 0-10 VCD, 0 - 5kOhms, Temperature PT100, PT500, PT1000, NI1000 and Temperature Thermocouples Type J, K; Accuracy: current and voltage ±0,05% of full scale, Resistance: ±0,1% of full scale, Temperature RTD: ±0,2°C, Temperature Thermocouples: ±0,4°C; Power Supply: 9-35VDC; Resolution: 20-bit; Sampling Rate: 7 sample/second (total); Temperature stability: max. ±30 ppm/°C; Dimensions: 107.6 x 89.7 x 62.2 mm; DIN rail mounted