Modbus Organization

Advantages of Joining | Join Form | Toolkit | Subscribe to Newsletter

Text Size: smallmediumlarge
 Back to Company

 

PiiGAB

MBus2Modbus

Type:  Network Gateway
Description:  Gateway/converter series developed for remote reading of M-Bus meters with up to four clients simultaneously. With this product it is possible to parallel connect a Modbus client to read values from an M-Bus meter to a PLC/RTU or to be shown on a local display. The gateway includes the option of a Modbus server. The Modbus server can be used independently or together with external systems such as SCADA systems or configuration tools.
Connectivity:  Modbus RTU, Modbus TCP
Features:  Up to four parallel clients; 2 x 10/100 Mbit Ethernet; TCP, UDP, Serial (configurable); Fixed IP address or dynamic via DHCP; Operative system independent; Modbus TCP/RTU Slave; Acts as an M-Bus meter on the M-Bus net; Read out the M-Bus network electricity and voltage levels; High security
Specifications:  Modes: TCP/RTU; Function codes: 03/04; Data types: INT16/UINT16/INT32/UINT32/INT64/UINT64/ FLOAT/DOUBLE FLOAT/STRING; Parameters: StationId, FloatMode; Register area: 0-65535; M-Bus Object to read: Value; M-Bus Header to read: Identification number, Manufacturer identification, Version identification, Device type identification, Access number, Status byte, Configuration field; Ports: 1xRJ45 for Ethernet (Option Eth2), 1xRS232, 1xRS485, 1xM-Bus slave, 1xM-Bus master; Operating system: Full Linux 2.6; Power supply: 24V DC or AC (local power); Coating: IP 20